Listed SIP and PIP lengths
The company profile lists these lengths for selected GI or copper inner-conductor constructions.

GI earthing electrodes
GI chemical earthing electrodes in 2, 3 and 6 metre SIP and PIP formats from 3E Solutions, with model-specific CPRI and JVVNL documents.
Discuss your requirementStart here
A GI chemical earthing electrode is a practical choice when the approved design permits galvanized construction and the soil exposure, fault duty and service plan suit it. Price alone is a weak basis for the decision.
3E Solutions lists galvanized SIP and PIP electrodes in 2, 3 and 6 metre lengths, with sections that vary by model. Test reports and JVVNL approvals apply to named constructions, not every GI product in the range.
The company profile lists these lengths for selected GI or copper inner-conductor constructions.
Pipe, strip and connection details must be taken from the selected model schedule.
Ask for the test report, GTP or approval that matches the offered construction.
Technical view


The 3E profile lists 50 mm and 80 or 88 mm outer sections across the SIP and PIP family. A separate JVVNL PM-KUSUM approval describes a 3000 mm GI pipe with 50 mm ID, 58 mm OD and a 25 x 6 mm GI strip for the specified set.
One CPRI report records a galvanized 88 mm OD, 80 mm ID, 3000 mm electrode with copper strip that complied at 33 kA rms for 1 second and 70 kA peak. That result belongs to that model.
An undersized connection, damaged coating, loose refill soil or a pit placed too close to another earth can spoil the installation. The finish may still look new, which is why the handover reading matters.
Keep the full electrode in useful soil, premix the conductive backfill with water and leave the terminal accessible. Separate earthings need at least 2 metres of clear spacing.
Specification
Name the duty and the construction. A request for a generic GI pipe leaves the test rating, terminal and installation package undefined.
Method
Match the model to the fault duty and site first. Installation then follows the approved drawing and ends with a recorded earth reading.
Confirm the earth function, fault requirement and model evidence.
Use the full specified length and keep separate earthings at least 2 metres apart.
Premix the compound with water and keep useful mother earth around the pit.
Check the accessible connection and record the installed resistance.
Questions from site and procurement teams
Yes. The supplied 3E profile lists 2, 3 and 6 metre SIP and PIP options. Availability and section still depend on the selected model.
No. JVVNL approvals name specific constructions, dimensions and GTPs. Match the offered model to the approval document instead of treating approval as a brand-wide label.
No. Coating choice does not establish the installed resistance. Test after installation and keep the chamber and terminal available for later inspection.
Bring us the site details
Send the duty, dimensions, fault requirement and approval clause. We will identify the relevant 3E model and supporting document.